PARTS REQUIRED:
- UTM key for bracket removal
- Phillips Head Screwdriver
- UTM activation wand (magnet)
- Float Gauge / Dial SC645 (magnetic mount)
- UTM back bracket
- Port plug
- UTM
STEP 01 - Record reading and remove old dial.
STEP 02 - Install sender. Refer to SC645 Sender Install guide for alternate Gauge Instructions.
WARNING: Ensure adapter recess is aligned under the cable.
STEP 3 - Confirm reading is identical.
WARNING: This step is critical to complete before proceeding.
STEP 04 - Firmly insert Port Plug into Socket B to ensure proper sealing. Firmly insert connector into socket A to ensure proper sealing. The UTM will begin to activate automatically; Watch for solid green to confirm successful communication.
WARNING: Confirm O-Rings are in place.
STEP 05 - Attach bracket.
STEP 06 - Align on tank central axis.
WARNING: For reliable communications, select location not closer than 15cm / 6'' from metal fittings (e.g. tank lid).
STEP 07 (OPTIONAL) - If manual activation is required, hold the activation wand in place for 6 seconds. Watch for solid green to confirm successful communication.
NOTE: If bracket removal is required during service or install, insert removal key into keyslot.
For additional install options, support and enquiries, please contact ANOVA:
T: (844) 493-7762
IMPORTANT: Hazardous Area Control Drawing AD000029 supplied by ANOVA on request.